Test Files:
10MB
100MB
Chicago, Illinois
725 South Wells Street
Chicago, IL 60607
Facility Details:
* Raised floors
* 6,000 sq ft (expandable to 30,000 sq ft)
* Floor Load—250lbs per sq ft
* Power Density—Up to 10kW per cabinet
* 24×7 Technical Support Staff On-site
Infrastructure:
* Generator Capacity—1.5MW Caterpillar (expandable to 3x 1.5MW +
pull-up generator tap)
* UPS Capacity—750 kVA Chloride UPS N+1, 15 minute battery capacity
(expandable to 4.5 MW)
* Utility Power—5MW
* CRAC—4×70 ton Stulz Units, N+1 (expandable to 20×70 ton)
* Fire Suppression—VESDA particulate detection, clean agent
extinguishers,
Pre-action dry pipe sprinkler
* Chillers—230+ ton Smardt Units N+1 Chillers, 2N Pumps (expandable
to 1050 tons)
Network
* Fiber Diversity—Dual fully diverse fiber paths, building entry
points, and
in-building riser
* Available Networks—Atlantic Metro Communications, Steadfast
Networks, Abovenet, AT&T, Verizon, Qwest, Level(3) & RCN
* Transport Services—1.25Gbps, 10Gbps DWDM Waves, Layer 2 Transport
to 600/700 Federal (Abovenet) & 350 East Cermak (TelX/MMR & Equinix)
* Internal Cabling—Cat6/6a for 10Gbps Ethernet, SMF/MMF available,
overhead
fiber trays
Security
* Proximity card access controls
* 24×7 camera monitoring & recording